Instruction 14- mov dword – Maple Systems MAPware-7000 User Manual
Page 36

MAPware-7000 Ladder Logic Guide
28
1010-1041 rev. 00
Instruction 14- MOV DWord
Expression:
Space Requirement: 1 line x 5 column Location Requirement: Middle, Right rail
Function:
When the input is ON, the double-word (32-bit) data of A+1× A is stored in double-word register
B+1× B. The data range is -2147483648 to 2147483647.
Execution Condition:
Input
Operation
Output
OFF
No execution
OFF
ON
Execution
ON
Operand:
Coil or Bit
Register
Constant
Index
Name
X Y
B
S
T.
C.
M
X
W
Y
W
B
W
S
W
T C
D
I
J
K
M
W
A
Source
√
√
√
√
√
√
√
√
√
√
√
√
B
Destination
√
√
√
√ √
√
√
√
√
√
Example:
When B011 is ON, a double-word data of D0101×D0100 is stored in BW17×BW16 and the
output is turned ON. If D0101×D0100 is 1234567, the data 1234567 is stored in BW17ЧBW16.