Instruction 90- Step Sequence Input
Expression:
Space Requirement: 1 line x 3 column Location Requirement: Middle
Function:
When the input is ON and the device A is ON; the output is set to ON.
Execution Condition:
Input
Operation
Output
OFF
No execution
OFF
ON
When A is ON
ON
When A is OFF
OFF
Operand:
Coil or Bit
Register
Constant
Index
Name
X
Y B
S
T.
C.
M
X
W
Y
W
B
W
S
W
T C
D
I
J
K
M
W
A
Step Device
√
Example:
The following sequential operation is performed.
When B020 is changed from OFF to ON, B400 is set to ON and subsequent 9 devices (B401 to
B409) are reset to OFF.
When X004 comes ON, B400 is reset to OFF and B401 is set to ON.