IAI America PCON-CFA User Manual
Page 37
3. SCON-CA/CF
A
31
(* In the table, ON indicates that the applicable bit is “1,” while OFF indicates that the applicable bit is “0.”)
Signal type
Bit
Symbol
Description
Details
Current position
32 bit
-
32-bit signed integer indicating the current position.
The unit is 0.01 mm.
(Example) Reading: 000003FFH = 1023 (decimal) = 10.23 mm
* If this data is read as a hexadecimal, a negative value is
indicated by a 2’s complement.
3.6 (1)
Completed
position number
(simple alarm
code)
16 bit
PM1 ~
PM512
16-bit integer.
After the actuator has moved to the target position and entered
the positioning band, the position number corresponding to the
completed positioning is output.
“0” is output when no position movement has been performed
yet or while the actuator is moving.
If an alarm occurs (= the ALM status signal turns ON), a
corresponding simple alarm code (refer to the operation
manual for the controller) will be output.
3.6 (1)
b15 EMGS
Emergency stop: An emergency stop is being executed when
the signal is ON.
3.4.7 (2)
b14 PWR
Controller ready: The signal turns ON when the controller
becomes ready.
3.4.7 (1)
b13 ZONE2
Zone 2: The signal is ON when the current position is inside
the specified zone.
3.4.7 (12)
b12 ZONE1
Zone 1: The signal is ON when the current position is inside
the specified zone.
3.4.7 (12)
b11 PZONE
Position zone: The signal is ON when the current position is
inside the specified position zone.
3.4.7 (12)
b10 MODES
Teaching mode signal: The signal is ON when the teaching
mode is selected.
3.4.7 (16)
b9 WEND
Position data read complete: The signal turns ON when the
position data read is complete.
3.4.7 (17)
b8 RMDS
Operation mode: The signal is OFF when the current mode
AUTO, or ON when the current mode is MANU.
3.4.7 (19)
b7
b6
-
Cannot be used.
-
b5 PSFL
Missed load during push-motion operation: The signal turns
ON when the actuator missed the load during push-motion
operation.
3.4.7 (23)
b4
SV
Ready: The signal is ON when the servo is ON.
3.4.7 (5)
b3
ALM
Alarm: The signal turns ON when an alarm occurs.
3.4.7 (3)
b2
MOVE
Moving signal: The signal is ON while the actuator is moving.
3.4.7 (9)
b1 HEND
Home return complete: The signal turns ON when the home
return is completed.
3.4.7 (6)
PLC in
put
Status signal
b0 PEND
Positioning complete signal: The signal turns ON when the
positioning is completed.
3.4.7 (10)