7 profibus-dp parameters – IAI America PCON-CFA User Manual

Page 156

background image

4. SCON-CA


150

4.7 PROFIBUS-DP

Parameters


The parameters relating to PROFIBUS-DP are parameter Nos. 84 to 87, 90 and 159.

Category: C: External interface parameter

No. Category Symbol

Name

Factory

default

1

~

83

For parameter Nos. 1 to 83, refer to the operation
manual for the controller.

84

C

FMOD

Fieldbus operation mode

0

85

C

NADR

Fieldbus node address

1

86

C

FBRS

Fieldbus baud rate

0

87 C NYTP

Network

type

3

90

C

FMIO

Fieldbus I/O format

0

159

C

FBVS

FB Half Direct Mode Speed Unit

0

z Fieldbus operation mode (No. 84 FMOD)
Specify a desired operation mode in parameter No. 84 using a value between 0 and 4.

Set value of

parameter No. 84

Mode name

Number of

occupied bytes

Description

0 (factory setting) Remote I/O mode

2

The actuator is operated by PIOs (24-V I/Os) via
PROFIBUS-DP.

1

Position/simple
direct mode

8

The target position can be specified directly as a
value or using a value in the position data table.
Other values required for operation are set in the
position data table.

2

Half direct mode

16

Operate the actuator by specifying the speed,
acceleration/deceleration and push-current value,
in addition to the target position, directly using
values.

3

Full direct mode

32

Operate the actuator by specifying all values
relating to position control directly using values.

4

Remote I/O mode 2

12

The current-position and current-speed read
functions are added to the functions available in the
remote I/O mode.

z Fieldbus node address (No. 85 NADR)
Specify the slave number of the remote station in parameter No. 85.

Setting range: 0 to 125 (The factory setting is 1.)

z Fieldbus baud rate (No. 86 FBRS)
The baud rate is automatically set according to the corresponding setting on the master side and thus need not be
set.