Rev 1.3 Series X11CA Computer Annunciators: X11CA Configuration Software User’s Manual

4. X11CA Software Operation

Hardware Control-© 2003 Ronan Engineering

35

If the input is normally energized:

§ When the Field Contact goes into alarm

condition, the audio device becomes
inactive.

§ When the horn is silenced, the audio

display turns ON.

LAMP
ALARM

If the input is normally not energized:

§ When the Field Contact goes into alarm

condition, the lamp starts fast flashing.

§ When the alarm is acknowledged, the

lamp becomes steady ON.

§ When the alarm returns to normal, the

lamp goes OFF.

If the input is normally energized:

§ When the Field Contact goes into alarm

condition, the lamp starts fast flashing.

§ When the alarm is acknowledged, the

lamp goes OFF.

§ When the alarm returns to normal, the

lamp goes ON.

Table 4-15 Selection of Signals Transistor Output follows

Normally Energized option for the transistor output

When FC, ACK, ALARM or HORN is chosen for the transistor
output-triggering signal, the Normally Energized check box
becomes activated. By default, the transistor output is set to
Normally Not-Energized. When this box is checked, the state of an
event gets reversed, so that it stays active in its normal state, but
inactive in its alarm state.

Dual Output option for the transistor output

This option is available in the future. Once this option is activated,
the Transistor A signal from the micro controller activates both the
transistors A and C, the Transistor B signal activates both the
transistors B and D.