Rev 1.3 Series X11CA Computer Annunciators: X11CA Configuration Software User’s Manual

4. X11CA Software Operation

Hardware Control-© 2003 Ronan Engineering

31

? Auxiliary Relay Output Follow

Choose the signal that will trigger the
Auxiliary Relay Output signal from the
X11CA-IM when the switch on the
X11CA-IM is on Run side. The result
depends on the sequence type of each
channel.

Figure 4-19 Auxiliary Relay

Output

Example: The following is the sequence of A-1 type inX11CA-IM
environment.

Signal to Trigger
Auxiliary Relay
Output

Description

No AUX

(No Auxiliary Relay
Output)

Auxiliary Relay output is not available.

FC
(

Field Contact

)

If the Field Contact input is not normally energized:

§ When the Field Contact goes into an alarm

condition, auxiliary output becomes
energized.

§ When the Field Contact returns to normal

condition, auxiliary output becomes de-
energized.

If the Field Contact input is normally energized

§ When the Field Contact is in an alarm

condition, auxiliary output becomes de-
energized.

§ When the Field Contact returns to normal

condition, auxiliary output becomes
energized.

ACK
(

Acknowledge

)

If the Field Contact input is not normally energized

:

§ When the Field Contact goes into an alarm

condition, the auxiliary output becomes
energized.

§ When the acknowledge button connected to