Rev 1.3 Series X11CA Computer Annunciators: X11CA Configuration Software User’s Manual

4. X11CA Software Operation

Hardware Control-© 2003 Ronan Engineering

32

the X11CA-IM is pressed, auxiliary output
becomes de-energized.

If the Field Contact input is normally energized

§ When the Field Contact goes into alarm

condition, auxiliary output becomes de-
energized.

§ When the alarm is acknowledged on the

X11CA-IM, the auxiliary output becomes
energized.

ALARM
(

Alarm Simulator

)

If the Field Contact input is not normally energized:

§ When the Field Contact goes into alarm

condition, auxiliary output becomes
energized.

§ When the alarm is acknowledged, auxiliary

output stays energized.

§ When the alarm returns to normal, auxiliary

output becomes de-energized.

If the Field Contact input is normally energized:

§ When the Field Contact goes into alarm

condition, auxiliary output becomes de-
energized.

§ When the alarm is acknowledged, auxiliary

output stays de-energized.

§ When the alarm returns to normal, auxiliary

output becomes energized.

HORN 1& 2

If the Field Contact input is not normally energized

:

§ When the Field Contact goes into alarm

condition, the audio device becomes active.

§ When the horn is silenced, the audio display

goes OFF

If the Field Contact input is normally energized:

§ When the Field Contact goes into alarm

condition, the audio device becomes
inactive.

§ When the horn is silenced, the audio display

turns ON.

Table 4-14 Selection of Signals the Auxiliary Relay Output Follows