Ronan X11CA Software Manual User Manual
Page 36
Rev 1.3 Series X11CA Computer Annunciators: X11CA Configuration Software User’s Manual
4. X11CA Software Operation
Hardware Control-© 2003 Ronan Engineering
32
the X11CA-IM is pressed, auxiliary output
becomes de-energized.
If the Field Contact input is normally energized
§ When the Field Contact goes into alarm
condition, auxiliary output becomes de-
energized.
§ When the alarm is acknowledged on the
X11CA-IM, the auxiliary output becomes
energized.
ALARM
(
Alarm Simulator
)
If the Field Contact input is not normally energized:
§ When the Field Contact goes into alarm
condition, auxiliary output becomes
energized.
§ When the alarm is acknowledged, auxiliary
output stays energized.
§ When the alarm returns to normal, auxiliary
output becomes de-energized.
If the Field Contact input is normally energized:
§ When the Field Contact goes into alarm
condition, auxiliary output becomes de-
energized.
§ When the alarm is acknowledged, auxiliary
output stays de-energized.
§ When the alarm returns to normal, auxiliary
output becomes energized.
HORN 1& 2
If the Field Contact input is not normally energized
:
§ When the Field Contact goes into alarm
condition, the audio device becomes active.
§ When the horn is silenced, the audio display
goes OFF
If the Field Contact input is normally energized:
§ When the Field Contact goes into alarm
condition, the audio device becomes
inactive.
§ When the horn is silenced, the audio display
turns ON.
Table 4-14 Selection of Signals the Auxiliary Relay Output Follows