beautypg.com

Ronan X54-3402 User Manual

Ronan Equipment

background image

Page 1 of 2

Rev. 0

A Family of

Products!!!

Transmitters

Alarm Trips

I/I Isolators

Ronan Engineering Company

Ph: 800-327-6626 Fax: 818-992-6435 E-mail: [email protected] Web: www.ronan.com

High Density Dual Channel Packaging

Field Configurable Options Including:

four (4) RTD types, seven (7) standard input spans

with selectable zero offsets, and relay operation

Full Input/Output/Power and Channel Isolation
Front Panel Power/Sensor Fail LED Indicator
Front Access to Zero, Span and Setpoint Controls
Standard 35 mm DIN Rail Mounting

DESCRIPTION:

The X54-3402 is a dual channel RTD alarm trip

powered by 24 vdc. Features include: two piece plug-in connectors for
easy wiring and maintenance; Power/Sensor Fail LEDs; field configur-
able ranges and RTD types; 1000 vac isolation; and front panel
ZERO, SPAN, and setpoint adjustments. RFI protection, wide operat-
ing temperature, and high accuracy are standard. Dual setpoints are
user configured for high or low and have adjustable deadband. Output
relays are form “C” and can be normally energized or de-energized.
Custom inputs, outputs, and scaling are available from the factory.

RTD Alarm Trips - Field Configuration Options - High Density DIN Rail Packaging

X54-3402

Dual Channel Universal RTD Alarm Trip

ISO 9001

REGISTERED

SPECIFICATIONS:

Input:
RTD sensor types: 100 ohm platinum, 120 ohm nickel,

10 ohm copper. Factory or field configurable.

Input Ranges: Standard factory ranges or field configurable to

application requirements

Input Impedance:

> 100 K ohms.

Setpoint Adjustment:

Front-accessible, multi-turn, infinite resolution potentiometer
2 setpoints per channel. Field select normally energized or
de-energized and high or low setpoint relay operation.

Setpoint Repeatability: +/- 0.1% of span
Alarm Indication:
Front panel Red LED for each setpoint
Power On/Sensor Failure Response:
Green “Power On” LED turns Red if sensor fails. Up scale

drive on sensor failure is standard.

Response Time:
100 milliseconds.
Hysteresis:

Internal adjustments provide deadband adjustment from ap-
proximately 1-15% of range.

Contact Outputs:
One set of normally open and closed contacts per setpoint.
Contact Rating:
standard relays = 0.6 amps at 125 vac or 110 vdc, 2 amps at

30 vdc, (resistive loads)

optional relays = 14 amps at 120 vac, 10 amps at 240 vac, 8

amps at 24 vdc (resistive load; meets international standards)

Isolation: 1,000 V between channels.
Common Mode Voltage:
1000 volts peak AC maximum without damage.
Radio Frequency Effects:

< 0.4 mV (referred to input) + 0.2% of span (referred to out-
put) when exposed to 5W transmitter with frequency range
20-460 MHz at a distance of 1 m.

Ambient Temperature Range:
Operating: -20 to 158

°

F (-25 to 70

°

C).

Storage: -40 to 158

°

F (-40 to 70

°

C).

Power Supply Range:
18 to 30 VDC.

(max. current in alarm state = 190 mA@ 24 vdc)

Terminals:

High temperature polyester type, wire size 12 AWG max., 10
amps max., 300 V max.

Specifications apply at 23 +/- 2°C (74 +/- 2°F) unless otherwise specified, and are subject to change without notice,