Model 9060Z Manual 

 

48 

 

 

 

level. With heated probes this relay will be de‐energised while the probe is heating up from ambient, 
making the contacts open circuit. 

30. ‘Cal 1 in Progress’ 
31. ‘Cal 2 in Progress’ 
A calibration check is occurring, either manual or automatic mode. 

32. ‘Purge 1 in Progress’ 
33. ‘Purge 2 in Progress’ 
A probe purge is occurring, either manual or automatic mode. 

9.3 ALARM RELAY OPTIONS 

The three process alarm relays (relays 1 to 3) are user defined. The relay action will depend on the 
selections made in the COMMISSIONING menu functions #45 to #48. 

The relay contacts are all designed to be “Fail Safe”. That is, they are 

 open when the transmitter power is off 
 closed when there is NOT an alarm condition 
 open when an alarm occurs 

The contact will close circuit again (relay energised) when the alarm condition is acknowledged. 

Choose to have the relays react to any or all of the following alarms or warnings – 

Oxygen on probe 1 Low  

Alarm  

Oxygen on probe 2 Low  

Alarm  

Oxygen on probe 1 Very Low  

Alarm  

Oxygen on probe 2 Very Low  

Alarm  

Oxygen on probe 1 High  

Alarm  

Oxygen on probe 2 High  

Alarm  

Oxygen Deviation High  

Alarm  

Probe 1 Temperature Low  

Warning  

Probe 2 Temperature Low  

Warning  

Calibration check on probe 1 in 
Progress  

Warning  

Calibration check on probe 2 in 
Progress  

Warning  

Purge on probe 1 in Progress  

Warning  

Purge on probe 2 in Progress  

Warning  

In addition to the above process alarms that can activate the process alarm relays, any of the common 
alarm  relay  events  that  have  been  taken  off  the  common  alarm  list  in  COMMISSIONING  menu 
function #49 will appear on the process alarm relay lists in function #46 to #48.