9 process input setup – Micromod MOD: 30MLTraining Manual User Manual
Page 43

Training Manual
Single Loop Template Lab
3.3.9 Process Input Setup
1 Press
NXT
PROC INP
will be displayed on line 2. We are
entering the process input setup for our PID
control loop.
2
Press DOWN
This takes you into the process input definition
menus. SLOT will be displayed on line 2.
3
BI 1 AIN
is the default input. We will
accept this.
This is Built-In Analog Input 1. Inputs may be
defined as NONE, BI AIN 1, BI AIN 2 or module
slot S01- to S11- for input being configured
4 Press
NXT
INP TYPE
will be displayed on line 2.
Figure 3 .16.
5
VOLTS
is the default for the process input.
Press UP and then ENT to change this
to CURRENT.
Input types may be defined as: VOLTS, MVOLTS,
CURRENT, RESIST, THRMOCPL
1 Slot: RTD2WIRE, CURRNT2W
2 Slots: RTD3WIRE, WIDERES
Built-in only: TC W/CJC, RTD
6
Press NXT until LO SIGNL is displayed on
Line 2
7
Press the DOWN arrow and FST/SLO
keys to change the low signal range to 4
Built-in analog input 1 is wired to a pot in the
demonstration unit which has a range of 0 to 6
Volts
8 Press
NXT
HI SIGNL
is displayed on line 2
9
Use the UP and FST keys to change the
high signal range to 20 and press ENT
10
Press NXT until HI ENGU is displayed on
line 2
11
Use the UP/DOWN keys and the FST
Pressing the Up key, will cause the Least
3 - 17