Sequence Display Lab
5. Press the SCROLL key next to the flashing ENT (enter)
If the display times out before you can
press Enter, simply press the UP or
DOWN key again.
6. The top line will change to CHARGE. The millisecond time
displays the elapsed time in the current step.
7. Change the display on the controller front panel to PID-100. Use
the Scroll key to display Setpoint.
8. In Vizapp, double-click on the LSH block.
9. Change the mode to Manual and set the Result to ON.
The sequence enters the HEAT step
The controller changes to AUTO mode
with a setpoint of 90
10. Change the result back to OFF and the mode to AUTO, then
close the block.
11. Using the potentiometer, slowly raise the process temperature to
90
When the temperature reaches or exceeds
90, the sequence enters the COOK stage.
12. On the controller, switch to the sequence display
The top line shows COOK, and line 2
shows the time in step. When 20 seconds
has elapsed the sequence proceeds to the
COOL stage.
13. Switch to the PID-100 display on the controller.
The setpoint should be 20.
14. Using the potentiometer, slowly decrease the temperature to 20
The sequence enters the DRAIN step and
the controller switches to Manual mode
with a setpoint of zero.
15. In the ViZapp database, open the LSL block. Change the mode
to MANUAL and set the result to ON.
The sequence goes to the IDLE step.