Micromod MOD: 30MLTraining Manual User Manual
Page 212

Training Manual
Process Alarm Display Lab
B - CONFIGURE A HIGH PROCESS ALARM
Step Procedure
Comments
4.
Double-click on the PAD block to open it
Refer to the next figure.
5.
Enter the tag name PALM_H in the Name field.
6.
Using the pull-down menu, change the Trip
Condition to Greater Or Equal
The alarm will activate (trip) when the
process value is greater than or equal to
the trippoint
7.
Enter a trip value of 150
Since the flow is 0 to 200 GPM, the alarm
will trip at 150 GMP or 75%
8.
Select the Display tab of the PAD block
Refer to the next figure.
9.
Change the Display Format field from “Float 6” to
“Float 1” by selecting it with the mouse
The numerical display of the alarm will be
floating point with one place to the right
of the decimal point
10.
In the Engineering Units field, type GPM
11.
Select “Normal” for the Bar Format field
The range fields are activated
12.
Leave the Lo Range at the default value of 0
13.
Change the Hi Range value to 200
14 - 2