beautypg.com

Micromod MOD: 30MLTraining Manual User Manual

Page 187

background image

Training Manual

Sequence Lab

Figure 12 .13.

SEQ Properties -
Inputs Tab

• Add more inputs to the SEQ block as below: Leave the initial value data field in its

default value.

Input #

Name

Type

2

LevelHI

Discrete

High Level Switch

3

Temp

Floating Point

Product Temperature

4

Draining

Discrete

Drain Valve Open Feedback Contact

5

HeatSP

Floating Point

Setpoint for Heating Product

6

CoolSP

Floating Point

Setpoint for Cooling Product

7

LevelLO

Discrete

Low Level Switch

Use the Modify button if you make a mistake. Select the input and then click on the
Modify button.

12 - 9

This manual is related to the following products: