Training Manual
Sequence Lab
•
Enter the Transition Expressions for the steps as shown below:
Step #
Step Name
Transition Expression
2 Charge
if LevelHI then Heat
3 Heat
if Temp >= HeatSP then Cook
4 Cook
if Time >= 0:0:20.0 then Cool
5 Cool
if Temp <= CoolSP then Drain
6 Drain
if LevelLO then Idle
• After adding all the steps, the Steps tab of the SEQ Properties dialog will look like the
figure below:
Figure 12 .22.
SEQ Properties -
Steps Tab
Remember, the Transition Expression defines what makes the sequence leave the
current step and go to another. TIME is a sequence block attribute which indicates the
time in the step. There is a timer that starts as soon as you enter each step, and resets
upon transition to the next one.
• Click on OK to close the SEQ block.
10. Make connections to the Sequencer:
• Select the Multi-segment connector from the Algorithms window and then click on the
LSL (DIM) block.
• The Choose Parameter dialog of the DIM block will be displayed next.
• Select R (Result) from the list (Refer to the next figure)
12 - 16