Wayne Vista 3 - DTU Installation

30. Install the DTU assembly on the horizontal cross

bracket as shown in Figure 14. Use the two
screws, washers, and nuts as supplied in the TS-
DTU/P hardware kit.

Figure 14: DTU Mounted

31. Attach ring terminal of ground wire to dispenser

bracket using screw and nut as shown. Coil
excess wiring and fi rmly attach with tie wraps to
ensure that it does not interfere with door closing.

Figure 15: Ground Wire Connected

32. Find cable assembly extending from TS-VFM vapor

meter in dispenser hydraulics enclosure.

33. Find wiring from previously installed potted nipple

assembly inside hydraulics enclosure.

34. Find two wire splice connector kits. Inside hydraulics

enclosure, connect black wire from potted nipple
assembly to black wire from TS-VFM fl ow meter by
putting each lead into an opening in the wire splice
connector and push fi tting closed to lock.

35. Find cable from TS-VPS inside hydraulics enclosure.

Clip yellow and blue leads from end of cable.

36. Find purple and white wires from potted nipple

assembly in hydraulics enclosure. Strip wiring
insulation 3/8” from end of wire.

37. Using wire nuts provided with kit connect purple wire

from potted nipple assembly to black wire of TS-VPS.
Connect white wire from potted nipple assembly to
white wire of the TS-VPS.

38. Reinstall lower hydraulic door using key-lock.

39. Close dispenser doors on each side of the unit and

fi rmly attach with two screws located in each door.