beautypg.com

Franklin Fueling Systems TS-DTU Data Transfer Unit Dispenser Retrofit Manual User Manual

Page 15

background image

15

Gilbarco Encore 300 and 500 - DTU Installation

34. Cut excess wire inside DTU allowing a length of

2” for terminal block wiring. Strip wire insulation
3/8” from the end. Connect wires to DTU terminal
block.

Figure 14: Wiring Connection to DTU

35. Reinstall barrier cover using screws from step 23.

Figure 15: Reinstall Barrier

36. Replace DTU cover.

Figure 16: Replace Cover

37. Find cable assembly extending from TS-VFM

vapor meter in dispenser hydraulics enclosure.

38. Find wiring from previously installed potted nipple

assembly inside hydraulics enclosure.

39. Find two wire splice connector kits. Inside

hydraulics enclosure connect black wire from
potted nipple assembly to black wire from TS-VFM
fl ow meter by putting each lead into an opening in
the wire splice connector and push fi tting closed to
lock.

40. Find cable extending from TS-VPS inside

hydraulics enclosure. Cut yellow and blue leads
from end of cable.

41. Find purple and white wires from potted nipple

assembly in hydraulics enclosure. Strip wiring
insulation 3/8” from end of wire.

42. Using wire nuts provided with kit, attach purple

wire from potted nipple assembly to black wire
of TS-VPS and white wire from potted nipple
assembly to white wire of the TS-VPS.

43. Attach lower hydraulics covers to dispenser and

secure each using key lock.

44. Close both main doors of dispenser. Securely

attach the two latches on the left side of each
interface door.

45. Close both interface doors and lock.