Franklin Fueling Systems TS-DTU Data Transfer Unit Dispenser Retrofit Manual User Manual
Page 15
15
Gilbarco Encore 300 and 500 - DTU Installation
34. Cut excess wire inside DTU allowing a length of
2” for terminal block wiring. Strip wire insulation
3/8” from the end. Connect wires to DTU terminal
block.
Figure 14: Wiring Connection to DTU
35. Reinstall barrier cover using screws from step 23.
Figure 15: Reinstall Barrier
36. Replace DTU cover.
Figure 16: Replace Cover
37. Find cable assembly extending from TS-VFM
vapor meter in dispenser hydraulics enclosure.
38. Find wiring from previously installed potted nipple
assembly inside hydraulics enclosure.
39. Find two wire splice connector kits. Inside
hydraulics enclosure connect black wire from
potted nipple assembly to black wire from TS-VFM
fl ow meter by putting each lead into an opening in
the wire splice connector and push fi tting closed to
lock.
40. Find cable extending from TS-VPS inside
hydraulics enclosure. Cut yellow and blue leads
from end of cable.
41. Find purple and white wires from potted nipple
assembly in hydraulics enclosure. Strip wiring
insulation 3/8” from end of wire.
42. Using wire nuts provided with kit, attach purple
wire from potted nipple assembly to black wire
of TS-VPS and white wire from potted nipple
assembly to white wire of the TS-VPS.
43. Attach lower hydraulics covers to dispenser and
secure each using key lock.
44. Close both main doors of dispenser. Securely
attach the two latches on the left side of each
interface door.
45. Close both interface doors and lock.