Franklin Fueling Systems TS-DTU Data Transfer Unit Dispenser Retrofit Manual User Manual
Page 11
11
Gilbarco Advantage Narrow Frame - DTU Installation
36. Attach ring terminal of DTU ground wire to
dispenser with bolt, nut and star washer.
Figure 17: Attach Ground Wire
37. Use wire-wrap ties to attach excess wires from AC
wiring harness together.
38. Use wire-wrap ties to attach excess wire from DTU
power harness and ground away from door and
gears.
39. Find cable assembly extending from TS-VFM
vapor meter in dispenser hydraulics enclosure.
40. Find wiring from previously installed potted nipple
assembly inside hydraulics enclosure.
41. Find two wire-splice connector kits. Inside hydraulics
enclosure, connect black wire from potted nipple
assembly to black wire from TS-VFM fl ow meter by
placing each lead into an opening in the wire splice
connector and push fi tting closed to lock.
42. Find cable extending from TS-VPS inside
hydraulics enclosure. Cut yellow and blue leads
from end of cable.
43. Find purple and white wires from potted nipple
assembly in hydraulics enclosure. Strip wiring
insulation
3
/
8
" from end of wire.
44. Using wire nuts provided with kit, attach purple
wire from potted nipple assembly to black wire
of TS-VPS and white wire from potted nipple
assembly to white wire of the TS-VPS.
45. Close main doors on Side A and Side B.
46. Engage main door latches located in both option
openings for each side. Refer to fi gure 2 & 3.
47. Tighten the three bolts at the bottom of each main
door assembly. See fi gure 1.
48. Reinstall side A lower dispenser door. Firmly
attach using key lock on right side of door.