Franklin Fueling Systems TS-DTU Data Transfer Unit Dispenser Retrofit Manual User Manual
Page 26
Wayne Ovation - DTU Installation
26
Figure 10: Push Wire to Electrical Enclosure
21. Push top of potted nipple assembly through
opening in electrical enclosure. Pull the wires
inside electrical enclosure through washer and
nut retained in step 18. Tighten potted nipple
assembly nut.
Figure 11: Install Potted Nipple
22. Find reducer in IS conduit kit. From electrical
enclosure, pull wires from the potted nipple
assembly through ¾” opening of reducer and
thread reducer to the top of the nipple assembly.
23. Find straight conduit fi tting from IS wiring kit.
From electrical enclosure, pull wires from the
potted nipple assembly through opening of
straight conduit fi tting. Turn straight conduit fi tting
clockwise onto reducer.
24. Remove two screws from IS wiring cover inside
the DTU and remove cover. Retain cover and
screws for future reassembly.
Figure 12: Remove Wiring Cover
25. Find 90-degree fi tting from IS conduit kit. Remove
nut from 90-degree fi tting. Attach fi tting to top
opening of DTU using nut previously removed.
Figure 13: Attach 90-Degree Fitting
26. Find fl exible conduit fi tting in IS conduit kit, 020-
1513. Using 90-degree fi tting and straight fi tting
installed earlier, determine length of fl exible
conduit needed and cut to fi t.
27. Pull wires inside electrical enclosure through IS
conduit assembly.
28. Remove nut and bushing from straight conduit
fi tting.