beautypg.com

Franklin Fueling Systems TS-DTU Data Transfer Unit Dispenser Retrofit Manual User Manual

Page 25

background image

Wayne Ovation - DTU Installation

25

Figure 6: Attach Power Connector to Board

10. Pull wires away from door using positioning

devices included with dispenser

11. Find ground wire from power wiring harness kit.

From end without ring terminal, strip 3/8” of wiring
insulation.

12. Attach ground wire to terminal block position

labeled GND of J2 on DTU.

13. Attach ring terminal of ground wire to dispenser

bracket using screw and nut as shown. Wind
excess wiring and attach with tie wraps to ensure
that it does not interfere with door closing.

Figure 7: Attach Ground Wire to Frame

14. Find the side of dispenser opposite of power

supply. Remove lower door on that side by
loosening two screws. Set door aside and save for
later assembly.

15. Remove nut from hole plug located at the bottom

of the electrical enclosure using two wrenches.
Remove bolt, nut, and washers and dispose of
them.

Figure 8: Remove Hole Plug

16. Find potted nipple assembly, 131610.

17. Remove and dispose of rubber washer from

assembly.

18. Turn top nut from potted nipple counter-clockwise

and remove nut and one washer by pulling it over
wire leads. Keep nut and washer for future use.

19. Using ¾” conduit hole punch, increase size of 1/2”

hole exposed after following step 14.

Figure 9: Increase Hole Size

20. Push wires from top of potted nipple assembly

up from the hydraulics enclosure through to the
electrical enclosure. Make sure that wiring is not
damaged by sharp edges.