Alarms and events
282
A
Alarm Dropout Ground Fault
Logged when current goes below dropout level of
ground fault alarm functionality.
GF Trip Priority Suspended
This event is no longer needed. We are simplifying
the implementation and removing dependencies
on ZSI type as well as ZSI enabled/disabled state.
As a result this event will be removed.
GF Trip Priority Resumed
This event is no longer needed. We are simplifying
the implementation and removing dependencies
on ZSI type as well as ZSI enabled/disabled state.
As a result this event will be removed.
GF Trip Priority Disabled MSGF
Optioned
Logged during initialization when GF Tripping
Priority function detects MSGF option in the system.
Function disables itself at this point
GF Trip Priority Operated
Logged when function modifies time delay of GF
protection element of any breaker that takes part in
GF tripping priority scheme.
High Current Transient Relay
HCTR Waveforms Max Count
Reached
Logged when maximum number of waveforms
have been triggered by the function
HCTR Waveforms Counter Reset Logged when user reset triggered waveform
counter
Alarm Pickup High Current
Trigger
Logged when current goes above pickup level.
Alarm Dropout High Current
Trigger
Logged when current goes below dropout level
Alarm High Current Trigger
Logged when function operated
Reduced Energy Let - Thru (RELT)
RELT Mode ON / OFF
Logged when a breaker goes into or out of RELT
mode
RELT Mode Multipoint ON / OFF
Logged when Multi-point goes into or out of RELT
mode
RELT Mode System Wide ON /
OFF
Logged when System Wide goes into or out of RELT
mode
RELT Mode - ON / OFF request
from Initiating Breaker
Logged when an associated breaker initiates RELT
mode on a breaker
See section
RELT Mode - ON / OFF request
from Modbus Device
Logged when a Modbus device initiates RELT mode
on a breaker
See section
Table A-9 Protection Relay Events
Event
Description
Notes and Troubleshooting tips