A.2.4 cpu settings related events – GE Industrial Solutions Entellisys 5.0 User Manual User Manual
Page 276

Alarms and events
264
A
A.2.4 CPU Settings Related Events
Unable to start Windows Time
Service. Time Synchronization
Failed
Logged by HMI on startup if it is not able to start the
Windows Time Service during initialization of the
time service routines. This impacts only HMI
synchronization, CPUs may be correctly
synchronized.
May be due to the operating system
permissions on the HMI. Login to the
computer as an administrator, navigate to
the time sync screen and toggle the Sync
HMI checkbox. See chapter 5.5 in DEH-500
the System Administrator’s manual for
troubleshooting
Caution: Unable to stop
Windows Time Service
Logged by HMI on shutdown if it is not able to stop
the Windows Time Service. Attempt to stop Time
service is performed only if it was not running
previously before starting HMI
Table A-4 HMI/CPU Communications Related Events
Event
Description
Notes and Troubleshooting tips
Table A-5 CPU Settings Related Events
Event
Description
Notes and Troubleshooting tips
Default CPU set to CPUA
The default view for the HMI has been set to CPU A
Default CPU set to CPUB
The default view for the HMI has been set to CPU A
Messnger Commission
Command Sent for Breaker
[Name]
Logged when a command to commission an
EntelliGuard Messenger is issued to a CPU
Messnger Decommission
Command Sent for Breaker
[Name]
Logged when a command to decommission an
EntelliGuard Messenger is issued to a CPU
Frequency Set To [50/60]Hz for
[CPUA/B]
Logged to record a change in the frequency setting
for a given CPU
Caution: Settings Failed Writing
Frequency to [CPUA/B]
Logged to indicate that a request to change the
system frequency of a given CPU was rejected
Also check the event log for communication
errors within the general time frame in which
this event occurred. See the communications
troubleshooting tips above if this is the case
(
).
Caution: Settings Failed Writing
Commission Status To [CPUA/B]
Logged to indicate that a request to change the
commissioning status of a given CPU was rejected
Also check the event log for communication
errors within the general time frame in which
this event occurred. See the communications
troubleshooting tips above if this is the case
(
).
Attention: System Freq
[50/60]Hz While CPU Synch
Clock Freq [60/50]Hz
Indicates a discrepancy between the frequency
jumper setting on the Hardware CPU sync clock in
the CPU chassis and the firmware setting in the
HMI / CPU
Verify that the jumper on the CPU synch clock
is set to the same system frequency as the
software setting.