GE Industrial Solutions Entellisys 5.0 User Manual User Manual
Page 275

Alarms and events description and system troubleshooting guide
263
A
IP Address in CPUB Written As
[n.n.n.n] From [n.n.n.n]
The IP address in CPU B has been changed as
specified.
Communications (other) related
Caution: Email Attempt
Failed.SMTP Error X
Indicates a problem reaching the specified e-mail
server.
For e-mail specific issues, in addition to the
general communications troubleshooting
tips above (
):
•
Verify that the specified e-mail server is
available and online.
•
Verify that the Firewall/VPN appliance (if
installed) is configured to permit this type
of traffic.
Email for Alarm Notification
Mail Sent OK
An attempt to send an alarm e-mail notification
was successful.
Email for Preventative
Maintenance Notification Sent
Out OK
An attempt to send a PM e-mail notification was
successful.
Clock and Time Synchronization Related
Time Synchronization Disabled Logged to record that the HMI is no longer
synchronizing the real-time clock on each CPU
Time Synchronization Enabled Logged to record that the HMI is now synchronizing
the real-time clock on each CPU
Time Synchronization
Frequency Set To [NN] Hours
Logged to record a change in the setting which
determines how often the HMI synchronizes the
real-time clock on each CPU
Time Synchronization
Successful
Logged each time the HMI synchronizes the
real-time clock on each CPU
Caution: Time Synchronization
Failed with [CPU A/B]
Logged when the HMI is unable to synchronize the
real-time clock of a given CPU
See the communications troubleshooting tips
above (
).
Caution: Daylight Savings Time
Error X
The HMI was unable to resolve the time zone
settings
Contact GE Post Sales Service (see
Daylight Savings Time in
Effect, Time Synchronized
Logged when a daylight savings transition and
resynchronization occurs
Standard Time in Effect, Time
Synchronized
Logged when a return to standard time and
resynchronization occurs
Time Synchronization
Successful
Logged the first time or first time since last failure
when HMI time sychronization is successful
Time Server Not Responding
Or Not Reachable
Logged once if time synch fails
See chapter 5.5 in DEH-500 the System
Administrator’s manual for troubleshooting
Table A-4 HMI/CPU Communications Related Events
Event
Description
Notes and Troubleshooting tips