Alarms and events
268
A
ZSI Zone 1…4 Enabled
ZSI functionality for zone 1…4 has been enabled
ZSI Zone 1…4 Disabled
ZSI functionality for zone 1…4 has been disabled
Protection Suspended ZSI File
Error
Bad or missing ZSI configuration file, functionality is
suspended
Contact GE Post Sales Service (see
Caution CPU Not Rcv From
Messngr
The CPU is not receiving data from a Messenger
Check Ethernet connection between the
Entellisys Messenger and switch, and the
connection between the switch and CPU.
Verify that Messenger is powered on and
operating.
CPU Receiving From Messngr
The CPU is receiving data from a Messenger
Attention Discrete IO Error
FlexLogic Disabled
Number of discrete I/O cards detected by CPU does
not match number that it has been programmed to
expect
Contact GE Post Sales Service (see
Attention Memory CRC Error
Replace CPU
CRC error has been detected in the CPU memory,
CPU should be replaced
Contact GE Post Sales Service (see
CPUA Assumes Control Logic
CPUA is running the control scheme
CPUA Relinquishes Control Logic CPUA is no longer running the control scheme
CPUB Assumes Control Logic
CPUB is running the control scheme
CPUB Relinquishes Control Logic CPUB is no longer running the control scheme
Attention Duplicate CPU IDs
Found
Both CPUs have the same ID
Contact GE Post Sales Service (see
Note CPU Internal Error 1
CPU detected an internal error
Contact GE Post Sales Service (see
Note CPU Internal Error 2
CPU detected an internal error
Contact GE Post Sales Service (see
Note CPU Internal Error 4
CPU detected an internal error
Contact GE Post Sales Service (see
Table A-6 CPU Status Events
Event
Description
Notes and Troubleshooting tips