Alarms and Events
151
8
• RELT Mode Multipoint - OFF Request From User
• RELT Mode Multipoint - ON Request From FlexLogic
• RELT Mode Multipoint - OFF Request From FlexLogic
• RELT Mode Multipoint - ON Request From Modbus Dvc
• RELT Mode Multipoint - OFF Request From Modbus Dvc
• RELT Mode Multipoint ON
• RELT Mode Multipoint OFF
System Wide RELT
• RELT Mode System Wide - ON Request From User
• RELT Mode System Wide - OFF Request From User
• RELT Mode System Wide - ON Request From FlexLogic
• RELT Mode System Wide - OFF Request From FlexLogic
• RELT Mode System Wide - ON Request From Modbus Dvc
• RELT Mode System Wide - OFF Request From Modbus Dvc
• RELT Mode System Wide ON
• RELT Mode System Wide OFF
Alarming
The Reduced Let Thru On Alarm is annunciated anytime either a user, Modbus or FlexLogic
turns on any Reduced Energy Let Thru mode (Single-point, Multi-point or System Wide)
regardless of the Reduced Energy status. If acknowledged, the HMI will re-alarm every X
(adjustable from 1 -24) hours until the system is returned to normal.
RELT Alarm Re-Alarm delay
To adjust the Re-alarm delay, On the Main Menu, click the User Settings button and click on
Alarms. From the Alarms screen click on RELT Alarm. The Re-alarm delay is adjustable from 1 to
24 hours.
Figure 8-8 RELT Re-Alarm