GE Industrial Solutions Entellisys 5.0 Integrator's Guide User Manual
Page 94

Modbus Memory Map
94
4
6E4F
Option Freq and Rev Pwr Relay Count
0 to 30
---
1
F001
0
6E50
Option Freq and Rev Pwr Relay Node x
Enable
0 to 4294967295
---
1
F722
0
6E52
Reserved (3 items)
---
---
---
---
---
6E55
Option HRGF Location Count
0 to 4
---
1
F001
0
6E56
Option HRGF Location Function x State
Enable
0 to 15
---
1
F722
0
Self Test Targets (Read Only)
6E64
Reserved (4 items)
0 to 4294967295
0
1
F143
0
Function X HRGF Location Settings (Read/Write Setting) (4 modules)
6E80
Function X HRGF Location Auto Mode
Enabled
0 to 1
---
1
F102
1
6E81
Function X HRGF Location Main Breaker
0 to 29
---
1
F001
0
6E82
Function X HRGF Location ReAlarm Delay
0 to 99
S
1
F001
8
6E83
Function X HRGF Location Alarm ReCheck
Delay
0 to 99
S
1
F001
2
6E84
Function X HRGF Location Trip Delay
0 to 999
S
1
F001
0
6E85
Function X HRGF Location Trip Enabled
0 to 1
---
1
F102
1
6E86
Function X HRGF Location Settings Reserved
(4 items)
F001
6E8A
...Repeated for module number 2
6E94
...Repeated for module number 3
6E9E
...Repeated for module number 4
Function X HRGF Location (Read/Write Setting)
6EA8
Function X HRGF Location Manual Mode
Start
0 to 1
---
1
F102
0
6EA9
Function X HRGF Location Contactor Fre-
quency
0.5 to 2
Hz
0.25
F001
1
6EAA
Function X HRGF Location Contactor Duty
Cycle
0 to 100
%
1
F001
50
6EAB
Function X HRGF Location Manual Function
To Start
0 to 4
---
1
F001
0
6EAC
Function X HRGF Location Manual Availabil-
ity
0 to 15
---
1
F500
0
6EAD
Function X HRGF Location Test Contactor
Pulsing
0 to 4
---
1
F001
0
6EAE
Function X HRGF Location Subinterval
5 to 60
s
5
F001
30