Main task heart beat, 02ff) fr, Command password – GE Industrial Solutions Entellisys 5.0 Integrator's Guide User Manual
Page 59: Entry, Setting password entry, 02a8 c, On 02a9 can, Cation 02a4, Command password entry, Tion 02a8

59
4
Passwords (Read/Write Command)
02A0
Reserved (4 items)
0 to 4294967295
---
1
F003
0
02A4
Command Password Entry
0 to 4294967295
---
1
F003
0
02A6
Setting Password Entry
0 to 4294967295
---
1
F003
0
Passwords (Read Only)
02A8
Command Password Status
0 to 1
---
1
F102
0 (Disabled)
02A9
Setting Password Status
0 to 1
---
1
F102
0 (Disabled)
02AA
Reserved (128 items)
---
---
---
---
---
Communication Status(Read Only)
02FF
Main Task Heart Beat
0 to 65535
---
1
F126
0
Zone Manager
032A
Current Topology State
0 to 255
---
1
F001
0
032B
Current Zone1 Topology
0 to 255
---
1
F001
1
032C
Current Zone2 Topology
0 to 255
---
1
F001
1
032D
Current Zone3 Topology
0 to 255
---
1
F001
1
032E
Current Zone4 Topology
0 to 255
---
1
F001
1
032F
Current Zone1 Topology PT Throwover
0 to 255
---
1
F001
1
0330
Current Zone2 Topology PT Throwover
0 to 255
---
1
F001
1
0331
Current Zone3 Topology PT Throwover
0 to 255
---
1
F001
1
0332
Current Zone4 Topology PT Throwover
0 to 255
---
1
F001
1
Event Recorder (Read/Write Command)
0346
Event Recorder Clear Command
0 to 1
---
1
F126
0 (No)
Energy Commands (Read/Write)
0347
Energy Clear Command
0 to 1
---
1
F126
0 (No)
Fault Report Commands (Read/Write)
0348
Fault Trigger Command
0 to 1
---
1
F126
0 (No)
Demand
0349
Demand Subinterval Length
1 to 60
---
1
F001
1
034A
Demand Subintervals Per Interval
1 to 15
---
1
F001
1
034B
Demand Reset All Command
0 to 1
---
1
F126
0
034C
Number Of Demand Resets All
0 to 4294967295
---
1
F003
0
034E
Last Demand Reset All DateTime
0 to 4294967295
---
1
F050
0
0350
Demand Log Clear All Command
0 to 1
---
1
F126
0