GE Industrial Solutions Entellisys 5.0 Integrator's Guide User Manual
Page 83

83
4
37DB
SRC X UV Alarm Enable
0 to 1
---
1
F102
0
37DC
SRC X UV Alarm Curve Type
0 to 1
---
1
F726
1
37DD
SRC X UV Alarm Pickup Setting
10 to 95
%
1
F001
50
37DE
SRC X UV Alarm Time Delay
0.5 to 600
---
0.5
F001
15
37DF
SRC X UV Alarm Phase Requirement
1 to 3
---
1
F001
1
37E0
SRC X UV Alarm Block Volt Enable
0 to 1
---
1
F102
0
37E1
SRC X UV Alarm Block Volt Setting
5 to 75
%
1
F001
5
37E2
SRC X OV Trip Enable
0 to 1
---
1
F102
0
37E3
SRC X OV Trip Pickup Setting
105 to 125
%
1
F001
120
37E4
SRC X OV Trip Time Delay
0.5 to 600
S
0.5
F001
30
37E5
SRC X OV Trip Phase Requirement
1 to 3
---
1
F001
1
37E6
SRC X OV Trip Open or Trip Setting
0 to 1
---
1
F727
1
37E7
SRC X OV Alarm Enable
0 to 1
---
1
F102
0
37E8
SRC X OV Alarm Pickup Threshold
105 to 125
%
1
F001
120
37E9
SRC X OV Alarm Time Delay
0.5 to 600
---
0.5
F001
15
37EA
SRC X OV Alarm Phase Requirement
1 to 3
---
1
F001
1
37EB
Source Settings Reserved 2 (7 items)
37F2
SRC X PL Trip Enable
0 to 1
---
1
F102
0
37F3
SRC X PL Trip Pickup Setting
8 to 50
%
1
F001
8
37F4
SRC X PL Trip Time Delay
0.5 to 600
S
0.5
F001
30
37F5
SRC X PL Trip Block Volt Enable
0 to 1
---
1
F102
0
37F6
SRC X PL Open or Trip Setting
0 to 1
---
1
F727
1
37F7
SRC X PL Alarm Enable
0 to 1
---
1
F102
0
37F8
SRC X PL Alarm Pickup Setting
8 to 50
%
1
F001
8
37F9
SRC X PL Alarm Time Delay
0.5 to 600
S
0.5
F001
15
37FA
SRC X PL Alarm Block Volt Enable
0 to 1
---
1
F102
0
37FB
SRC X PL Trip Voltage Setting
5 to 5
%
1
F001
5
37FC
SRC X PL Alarm Blocking Voltage Setting
5 to 5
%
1
F001
5
37FD
Source Settings Reserved 3 (3 items)
3800
SRC X Rev Power Trip Enable
0 to 1
---
1
F102
0
3801
SRC X Rev Power Trip Pickup Setting
10 to 990
kW
10
F001
990
3802
SRC X Rev Power Trip Time Delay
0.5 to 600
S
0.5
F001
30
3803
SRC X Rev Power Alarm Enable
0 to 1
---
1
F102
0