GE Industrial Solutions Entellisys 5.0 Integrator's Guide User Manual
Page 60

Modbus Memory Map
60
4
0351
Demand Log Last Cleared All Date
0 to 4294967295
--
1
F050
0
Waveform Capture
035D
Number WF Records Available
0 to 65535
---
1
F001
0
035E
Waveform Clear Command
---
---
---
F126
0
035F
Waveform Last Clear Date
0 to4294967295
---
1
F050
0
0361
Waveform Trigger Command
---
---
---
F126
0
0362
Waveform Trigger Mode
---
---
1
F118
0
0363
Waveform Trigger Position
0 to 119
half
cycles
1
F001
0
0364
Waveforms Since Last Clear
0 to 4294967295
---
1
F003
0
0366
Reserved (2 items)
0 to 65535
---
1
F001
0
0368
Waveform Trigger Thru FlexLogic
0 to 65365
---
1
F300
0
Preventive Maintenance (R/W)
0370
Load Life Rating 800A
0 to 65535
---
1
F001
2800
0371
Load Life Rating 1600A
0 to 65535
---
1
F001
2800
0372
Load Life Rating 2000A
0 to 65535
---
1
F001
2800
0373
Load Life Rating 3200A
0 to 65535
---
1
F001
2800
0374
Load Life Rating 4000A
0 to 65535
---
1
F001
2800
0375
Load Life Rating 5000A
0 to 65535
---
1
F001
2800
0376
Mechanical Life Rating 800A
0 to 65535
---
1
F001
2800
0377
Mechanical Life Rating 1600A
0 to 65535
---
1
F001
2800
0378
Mechanical Life Rating 2000A
0 to 65535
---
1
F001
2800
0379
Mechanical Life Rating 3200A
0 to 65535
---
1
F001
2800
037A
Mechanical Life Rating 4000A
0 to 65535
---
1
F001
2800
037B
Mechanical Life Rating 5000A
0 to 65535
---
1
F001
2800
037C
Load Life Max Current 800A
1 to 50
----
1
F001
15
037D
Load Life Max Current 1600A
1 to 50
----
1
F001
15
037E
Load Life Max Current 2000A
1 to 50
----
1
F001
15
037F
Load Life Max Current 3200A
1 to 50
----
1
F001
15
0380
Load Life Max Current 4000A
1 to 50
----
1
F001
15
0381
Load Life Max Current 5000A
1 to 50
----
1
F001
15
Hardware Information (Read Only)
03A0
Flash Lifetime
1 to 10
---
1
F001
1