Parker Hannifin

70 Aries User Guide

Inputs—Enable, Reset

The drive Enable and Reset inputs are optically isolated inputs. Current is
limited internally for input voltage control of 5 to 24 volt logic. The Anode (+)
and Cathode (

−) are on separate connector pins to allow significant flexibility

in wiring to different styles of interface.

Description

Min

Max

Units

Turn-on time

1

ms

Turn-off time

1

ms

Guaranteed on voltage

4

VDC

Guaranteed off voltage

2

VDC

Maximum forward voltage

30

VDC

Maximum reverse voltage

-30

VDC

Forward current

3

12

mA

Note:

All parameters are at the connector pin.

Table 30 Inputs—Enable and Reset Electrical/Timing Characteristics

Outputs—Encoder

Description

Min

Typical

Max

Units

Output Frequency
(pre-quadrature)

5

MHz

Input Voltage High *

2.4

V

Input Voltage Low *

0.5

V

* Based on 120Ω differential load impedance.

Note:

All parameters are at the connector pin.

Note:

Aries encoder is a hardware pass-through; therefore, you cannot change output

resolution.

Table 31 Outputs—Encoder Outputs Electrical/Timing Characteristics

Outputs—Fault

Description

Min

Typical

Max

Units

Blocking Voltage

30

V

Continuous Load Current

10

mA

Output Saturation Voltage
(at 1.0 mA)

1.0

V

* Based on 120Ω differential load impedance.

Note:

All parameters are at the connector pin.

Table 32 Outputs— Fault outputs Electrical/Timing Characteristics