Table 43 current foldback ratings, Figure 42 time until current foldback occurs, Difold – Parker Hannifin 88-021610-01G User Manual
Page 102
Parker Hannifin
102 Aries User Guide
DIFOLD
Current Foldback Enable
Type
Drive Configuration
Product Rev
Syntax
Aries 1.0
Units
b = enable bit
Range
Ø (disable) or 1 (enable)
Default
1
Response
DIFOLD: <*>Ø
See Also
none
The DIFOLD command enables (1) or disables (Ø) the drive’s current
foldback protection feature. The current foldback feature reduces the drive’s
continuous current output by 20% when sustained current has the potential
to overheat the drive. For the AR-20xE and AR-30xE drives, this feature is
always enabled.
Each drive has the specifications shown in Table 43. Note that current
ratings are for the drive, not for the motor.
AR-01xx
AR-02xx
AR-04xx
AR-08xx
AR-13xx
AR-20xE
AR-30xE
Drive Continuous Current
Rating (100%)
1.0
Arms
1.75
Arms
3.0
Arms
4.5
Arms
6.3
Arms
10
Arms
16
Arms
Max Current Rating
3.0
Arms
5.25
Arms
9.0
Arms
13.5
Arms
14.07
Arms
30
Arms
48
Arms
Max Time at Peak Current
Rating
3.375
sec
3.375
sec
3.375
sec
3.375
sec
8.64
sec
3.375
sec
3.375
sec
Table 43 Current Foldback Ratings
If your drive is operating above its continuous rating, see Figure 42 to predict
the number of seconds until foldback occurs. For example, the graph shows
that at the drive’s peak current rating (300% of continuous), foldback occurs
after 3.375 seconds.
Note:
For model AR-13xx, foldback occurs after 8.64 seconds at its peak
rating (225% of continuous).
Figure 42 Time until current foldback occurs