Table 9 ar-30xe power dissipation, Cabinet cooling calculations, Ep p − ∗ = 1 – Parker Hannifin 88-021610-01G User Manual
Page 27
Parker Hannifin
Chapter 2 Mechanical Installation 27
Figure 4 Cabinet losses for AR-30xE when connected to a Parker MPM1422CSJ motor
Shaft Power
Voltage
0W*
1500W
3000W
240 VAC
35W
103W
172W
* Drive enabled, zero torque.
Table 9 AR-30xE Power Dissipation
Cabinet Cooling Calculations
Use the motor’s speed torque curve to determine the torque when the motor
is at running speed for your application. If the torque is not known, use the
“knee” (where the peak-torque curve intersects the continuous-torque curve)
of the graphed motion—this assumes the worst-case scenario for continuous
motion.
(
)
DRIVE
MOTOR
MOTOR
LOSS
E
E
P
P
−
∗
=
1
P
LOSS
=
power dissipated to cabinet (Watts)
P
MOTOR
=
shaft power of the motor (Watts)
E
MOTOR
=
efficiency of motor (Percent), approximately 0.85
E
DRIVE
=
efficiency of Aries drive (Percent), approximately 0.90