Dmtip, Dmtinf – Parker Hannifin 88-021610-01G User Manual

Page 108

background image

Parker Hannifin

108 Aries User Guide

DMTINF

Motor Inductance Factor

Type

Motor

Product Rev

Syntax

DMTINF

Aries 1.0

Units

r = units

Range

Ш.ШШ to 1.ØØ

Default

1

Response

DMTINF <*>1.ØØ

See Also

CONFIG

,

DMTIND

,

DMTR

Auto-Setup

: When using a Parker motor and the Aries Support Tool, this

command is automatically set for the selected motor.
If you did not use the Aries Support Tool, are using non-Parker motors, or
sent an RFS command to the drive, the parameter is set to zero (0)—you

must manually set this parameter to a non-zero number. Otherwise, the drive
reports the configuration errors E1–Motor Configuration Error and
E3–Maximum Inductance = Ø, and shuts down the drive.
For a list of automatically configured commands, see

DMTR

.

The DMTINF command specifies the minimum motor inductance divided by
the maximum motor inductance. Setting DMTINF to 1.ØØ does not derate the

motor.
If the minimum value of the motor inductance is not known, use the nominal
inductance as listed on the motor’s nameplate (or set DMTINF1.ØØ)

DMTIP

Peak Current

Type

Motor

Product Rev

Syntax

DMTIP

Aries 1.0

Units

r = Amps-RMS

Range

Ш.ШШ to 4ШШ.ШШ : ±Ш.Ш1

Default

Ш.ШШ (DMTIP of Ø results in motor configuration
warning)

Response

DMTIP: <*>7.5Ø

See Also

DMTIC

,

DMTICD

,

DMTLIM

,

DMTR

,

TDIMAX

Auto-Setup

: When using a Parker motor and the Aries Support Tool, this

command is automatically set for the selected motor.
If you did not use the Aries Support Tool, are using non-Parker motors, or
sent an RFS command to the drive, the parameter is set to zero (0)—you

must manually set this parameter to a non-zero number. Otherwise, the drive
reports the configuration errors E1–Motor Configuration Error and
E9–Peak Current = Ø.
For a list of automatically configured commands, see

DMTR

.

The DMTIP command sets a limit that the commanded current cannot

exceed. This is typically set to three times the motor’s continuous current
rating (DMTIC) or less.

If DMTIP is set higher than the full-scale value calculated by DMTLIM
(torque/force limit) the new DMTIP value will be ignored.