must cross, cross them at 90° to each other. Keep wiring supported and
close to cabinet metalwork.
• Cables may require the use of ferrite core suppressors.
Some installations may require that you take additional EMC measures.
To further increase product immunity and reduce product emissions,
you may add clip-on ferrite absorbers to all cables. Parker recommends
ferrites with at least 200 ohm impedance at 100 MHz, such as the
following:
Steward Ferrite
Part number 28A2024
Fair-Rite Part
number
0443164151
Note:
These ferrites are available from Parker Hannifin, part number 47-015956-01.
For larger diameter cables (up to 0.722 in O.D.), Fair-Rite part number
0444176451 is recommended.
• Your Installation may require additional EMC installation hardware
(as shown in illustrations).
The following clamp kits are available from Parker:
Clamp Type
Parker Part Number
R-Clamp Kit (10 per) for models
AR-02xx to AR-13xx
R CLAMP KIT
R-Clamp Kit (10 per) for models
AR-20xE and AR-30xE
R LARGE CLAMP KIT
Clamshell Clamp Kit (2 per)
for all models
CLAMSHELL KIT
Table 62 Enclosure Mounting Clamps
Note:
The Control power input also requires a mains power line filter,
varistors, and fuses in order to comply with the relevant CE directives.