Error/alarm details – Parker Hannifin Dynaserv G2 User Manual
Page 180
Error/Alarm Details
Error number
1
Memory error
Error type:
[KIND_POR] Start-up error
Measures:
[TYPE_POR] Do not start up.
Long:
Short:
MemoryError
MemoryErr
Main cause:
An error is detected during memory check when the power is turned on.
[Subcode]
1: CPU built-in ROM sum error
2: RAM error
3: Flash ROM sum error
Action to take:
Contact us.
Error number
2
Interface board error
Error type:
[KIND_POR] Start-up error
Measures:
[TYPE_POR] Do not start up.
Long:
Short:
InterfaceBoardError
IFB_Err
Main cause:
Failed to initialize the interface board.
Action to take:
Contact us.
Error number
3
Battery alarm
Error type:
[KIND_ELS] Others
Measures:
[TYPE_ELS] Others
Long:
Short:
BatteryAlarm
BatteryAlm
Main cause:
Battery voltage for memory backup is low.
Action to take:
Replace with a new lithium battery.
Error number
4
Watchdog error
Error type:
[KIND_SYS] System error
Measures:
[TYPE_ELS] Others
Long:
Short:
WatchdogError
Watchdog
Main cause:
A watchdog timer error occurred. The driver will be set in the reset status.
Action to take:
Contact us.