Honeywell MS-9200UDLSE User Manual
Page 64
Programming
64
MS-9200UDLS PN 52750:E1 01/27/09
3.6.1 Autoprogram
Pressing 1 while viewing Programming Screen #1, will select the Autoprogram option,
which prompts the control panel to poll all devices installed on the SLC loop. The
primary purpose of autoprogramming is to allow the installer a fast and easy way to
bring the system on-line as quickly as possible. The first time the system is powered-
up, it should be autoprogrammed.
If the system is already programmed and Autoprogram is initiated, the system will only
add default values for newly installed devices.
When Autoprogram is selected, the control panel will begin autoprogramming the
system by communicating with each addressable device installed on the SLC loop.
While autoprogramming, the panel will display the following:
When Autoprogramming is completed, the control panel will display the type and
quantity of each device installed on the SLC loop similar to the following display:
In the preceding example, the display indicates that the SLC Loop has 55 addressable
detectors, 35 monitor modules and 30 control modules installed.
Pressing the ESC key will return the display to Programming Screen #1.
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
Programming Screen #1
AUTOPROGRAM
AUTOPROGRAMMING!
PLEASE WAIT
Autoprogram Progress Screen
# OF DET LOOP1 055
# OF MON LOOP1 035
# OF CON LOOP1 030
Autoprogram Result Screen #1