Honeywell MS-9200UDLSE User Manual
Page 117

Programming
MS-9200UDLS PN 52750:E1 01/27/09
117
Annunciator addressing is specific to the MS-9200UDLS control panel. The
following table describes the annunciator addresses and the corresponding
addressable devices that will be annunciated at each annunciator address.
The MS-9200UDLS must be programmed for the annunciators installed on the
system. Refer to "Annunciators" on page 115 for information on annunciator
programming. Make certain to program the annunciator addresses that have been
physically installed on the system.
Note: The 8 General System Status Points include the following:
ACS Annunciator Address
Annunciator Displays the Following Points
1
8 General System Status Points & Zones 1 - 56
2
Zones 57 - 99 & 4 NACs
3
SLC Loop, Module Addresses 1 - 64
4
not used
5
SLC Loop, Module Addresses 65 - 99
6
not used
7
not used
8
SLC Loop, Detector Addresses 1 - 64
9
not used
10
SLC Loop, Detector Addresses 65 - 99
11
not used
12
not used
13
not used
14
not used
15
not used
16
not used
17
not used
18
not used
19
not used
20
8 General System Status Points & Zones 1 - 56
21
Zones 57 - 99 & 4 NACs
22
SLC Loop, Module Addresses 1 - 64
23
not used
24
SLC Loop, Module Addresses 65 - 99
25
not used
26
not used
27
SLC Loop, Detector Addresses 1 - 64
28
not used
29
SLC Loop, Detector Addresses 65 - 99
30
not used
31
not used
32
not used
• General Alarm
• Alarm Silenced
• Battery Fault
• General Trouble
• System Off Normal
• NAC Fault
• General Supervisory
• AC Loss