Honeywell MS-9200UDLSE User Manual
Page 155
Programming
MS-9200UDLS PN 52750:E1 01/27/09
155
Pressing 3 while viewing Zone Setup screen will display the following screen:
Zones 97, 98 and 99 can be programmed for normal zone operation or for special
purpose applications. In the above illustration, the three zones are shown Off,
which means they can be programmed to function in the same manner as all other
zones, by assigning them to input and output devices in the Programming Zone
Assignment Screen.
Pressing 1 will cause the display to change to PAS 97 On. Each press of the 1 key
will cause the display to toggle between PAS 97 On and PAS 97 Off. When Zone 97
is programmed On, a PAS (Positive Alarm Sequence) activation of any smoke
detector will cause Zone 97 to activate. By assigning Zone 97 to a control module
in the Programming Zone Assignment Screen, an output device connected to the
control module can be used to indicate a PAS condition in the control panel. Do not
assign Zone 97 to a Notification Appliance Circuit when using this zone to indicate
a PAS condition.
Pressing 2 will cause the display to change to Pre-signal 98 On. Each press of the 2
key will cause the display to toggle between Pre-signal 98 On and Pre-signal 98
Off. When Zone 98 is programmed On, a Pre-signal activation of any device will
cause Zone 98 to activate. By assigning Zone 98 to a control module in the
Programming Zone Assignment Screen, an output device connected to the control
module can be used to indicate a Pre-signal condition in the control panel. Do not
assign Zone 98 to a Notification Appliance Circuit when using this zone to indicate
a Pre-signal condition.
Pressing 3 will cause the display to change to Two Stage 99 On. Each press of the 3
key will cause the display to toggle between Two Stage 99 On and Two Stage 99 Off.
Refer to "Two Stage Operation" on page 108 for a description of this feature.
SPEC PURPOSE ZONE
1=PAS 97 OFF
2=PRE-SIGNAL 98 OFF
3=TWO STAGE 99 OFF
Disable Screen