Honeywell MS-9200UDLSE User Manual
Page 139

Programming
MS-9200UDLS PN 52750:E1 01/27/09
139
Ademco Contact ID & SIA Formats
The information shown in Table 3.3 is automatically programmed for the Central Station phone
number Event Codes when the Ademco Contact ID or SIA Format is selected. Enter 0s for an
Event Code Setting to disable the report. Disabled reports will not get called to the Central
Station. The programmer may enable the Event Types in programming as described on the
previous page.
Table 3.3 Event Codes
Event Description
Ademco Contact ID
SIA
Active
Active
Restoral
PULL STATION
115
FA
FH
MON-USER-DEF-1
115
FA
FH
WATERFLOW
113
SA
SH
MON-USER-DEF-2
113
SA
SH
SMOKE (PHOTO)
111
FA
FH
DET-USER-DEF-1
111
FA
FH
SMOKE (ION)
111
FA
FH
DET-USER-DEF-2
111
FA
FH
HEAT DETECT
114
KA
KH
DET-USER-DEF-3
114
KA
KH
SMOKE DUCT-P
116
FA
FH
DET-USER-DEF-4
116
FA
FH
PHOTO W/HEAT
111
FA
FH
DET-USER-DEF-5
111
FA
FH
DUCT SUPERVISORY
200
FS
FV
DET-USER-DEF-6
200
FS
FV
PHOTO SUPERV
200
FS
FV
DET-USER-DEF-7
200
FS
FV
PHOTO ADAPT
111
FA
FH
DET-USER-DEF-8
111
FA
FH
PHOTO BEAM
111
FA
FH
DET-USER-DEF-9
111
FA
FH
not used
000
00
00
not used
000
00
00
not used
000
00
00
not used
000
00
00
not used
000
00
00
not used
000
00
00
not used
000
00
00
not used
000
00
00
not used
000
00
00
not used
000
00
00
MONITOR
110
FA
FH
MON-USER-DEF-3
110
FA
FH
not used
000
00
00
not used
000
00
00
SMOKE CONVEN
111
FA
FH
MON-USER-DEF-5
111
FA
FH
HEAT CONVENTIONAL
114
KA
KH
MON-USER-DEF-6
114
KA
KH
MEDIC ALERT
100
MA
MH
MON-USER-DEF-7
100
MA
MH
HAZARD ALERT
150
PA
PH
MON-USER-DEF-8
150
PA
PH
TORNADO ALRT
150
PA
PH
MON-USER-DEF-9
150
PA
PH
MON-PHONE
000
00
00
MON-USER-DEF-10
000
00
00
TAMPER
144
TA
TH
MON-USER-DEF-11
144
TA
TH
MON SUPERVISORY
200
FS
FV
MON-USER-DEF-12
200
FS
FV
MON SUPERV AUTO
200
FS
FV