Product Description

18

MS-9200UDLS PN 52750:E1 01/27/09

1.3 Controls and Indicators

LCD Display
The FACP uses an 80-character
(4 lines X 20 characters) high
viewing angle LCD display. The
display includes a long life LED
backlight that remains illuminated. If
AC power is lost and the system is
not in alarm, the LED backlight will turn off to conserve batteries.

LED Indicators
LED indicators are provided to annunciate the following conditions:

AC Power (green)

Fire Alarm (red)

Supervisory (yellow)

Trouble (yellow)

Maintenance/presignal (yellow)

Alarm Silenced signals (yellow)

Disabled (yellow)

Battery fault (yellow)

Ground fault (yellow)

Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD
display and LED indicators as listed above. The key panel, which is visible with the
cabinet door closed, has 25 keys, including a 16 key alpha-numeric pad similar to a
telephone keypad.

Function keys:

Acknowledge/Step

Alarm Silence

Drill

Reset (lamp test)

Service/program keys:

Keys labeled 1 to 9

* key

# key

0 (recall) key

1st Event key

Clear key

Escape key

Mode key

Four cursor keys (up, down, left and right)

Enter key

Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and
supervisory conditions.

HONEYWELL

LIFE SAFETY

SYSTEM ALL NORMAL

10:00A 012102

1

4

*

2

5

0

3

6

#

1

st

EVENT

ABC

DEF

GHI

JKL

MNO

PRS

TUV

WXY

QZ

-/.

CLR

7

8

9

ESC

ENTER

RECALL

ACK/STEP

ALARM
SILENCE

DRILL

HOLD 2 SEC

RESET

MODE

MAINTENANCE

ALARM

SILENCED

DISABLED

BATTERY

GROUND

SUPERVISORY

TROUBLE

AC POWER

FIRE ALARM

Figure 1.2 Membrane/Display Panel