Programming

MS-9200UDLS PN 52750:E1 01/27/09

131

The Drill Button Enable (DRL BTN ENABLE) option allows the programmer to
select whether the Drill button on any installed ANN-80 annunciator will function
normally or always be ignored. Pressing 3 while viewing the ANN-80 Options
Screen #2 causes the display to toggle between Drl Btn Enable Yes (Drill button
functions normally) and Drl Btn Enable No (Drill button never functions).

3.6.9.2 Onboard DACT

The Onboard DACT (Digital Alarm Communicator/Transmitter) provides
communication to a central station. Pressing 2 while viewing the Option Module
Screen will cause the following screens to be displayed:

3.6.9.2.1 Onboard DACT Enable
To enable the onboard DACT, press 1 while viewing Onboard DACT Screen #1
until the display reads Enabled Yes. The display will toggle between Enabled Yes
and Enabled No with each press of the key.

3.6.9.2.2 Primary Phone
Press 2 while viewing On Board DACT Screen #1 to program the type of primary
phone line being connected to the DACT. The following screen will be displayed:

To select the type, press 1 while viewing the Primary Phone Line screen. The
following screen will be displayed:

Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break
ratio of 67/33 or 3 to select Rotary dialing with a make/break ratio of 62/38.

OPTION MODULES
1=ANNUNCIATORS
2=ON BOARD DACT
3=PRINTER/PC

Option Module Screen

ON BOARD DACT
1=ENABLED YES
2=PRIMARY PHONE
3=SECONDARY PHONE

On Board DACT Screen #1

ON BOARD DACT
1=SERVICE TERMINAL
2=CENTRAL STATION
3=SUPERV PHONE LINE

On Board DACT Screen #2

ON BOARD DACT
PRIMARY PHONE LINE
1=TYPE TOUCHTONE

Primary Phone Line Screen

PHONE LINE
1=TOUCHTONE
2=ROTARY 67/33
3=ROTARY 62/38

Primary Phone Type Screen

This manual is related to the following products: