beautypg.com

Honeywell MS-9200UDLSE User Manual

Page 151

background image

Programming

MS-9200UDLS PN 52750:E1 01/27/09

151

Pressing 3 while viewing Program Check screen will cause a screen similar to the
following to be displayed:

The Zone No Output feature allows the programmer to view the zones which have not
been programmed to at least one output device (not including general alarm Zone 00).
The example in the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have
been programmed to an addressable detector with an address of 001 on loop 1 but have
not been programmed to any output devices. Use the up and down arrow keys to view
all the zones without output assignments.

3.7.4 Walktest

To perform a walktest, press 1 while viewing Maintenance Screen #2. The following
screen will be displayed:

The operator can press 1 to perform a silent walktest or 2 to perform an audible
walktest. Pressing 1 or 2 will cause the control panel to enter Walktest Mode and will
display the following screen:

From this screen, it is possible to view the walktest log, untested system points or a
summary of the addressable devices tested during the current walktest. The user can
select between any of these screens without interrupting the current walktest session.
The walktest session will not end until the Unit In Walktest screen is exited by pressing
the Escape key to return to the Walktest Screen.

ZONES NO OUTPUT
05 07 09 10 11 1D001

PROGRAMMING
1=WALKTEST
2=SYSTEM
3=ZONE SETUP

Maintenance Screen #2

WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW RESULT

Walktest Screen

UNIT IN WALKTEST
1=VIEW WALKTEST LOG
2=VIEW POINTS
3=VIEW SUMMARY

Unit In Walktest Screen

This manual is related to the following products: