Default programming, Appendix b – Honeywell MS-9200UDLSE User Manual

Page 197

background image

Default Programming

MS-9200UDLS PN 52750:E1 01/27/09

197

APPENDIX B

Default Programming

The following table provides a list of the programming options and their factory default
settings.

Program Option

Factory Default

Program Option

Factory Default

Detector Programming

Not Installed

Relay 1

Alarm

Detector Type

Smoke-Photo

Relay 2

Trouble (fixed)

Detector Verification

Off

Relay 3

Supervisory

Detector Walktest

Yes

Annunciator Terminal Mode

No

Detector PAS

No

Annunciator ACS Mode

No

Detector Presignal

No

UDACT

No

Detector Zone Assign.

000 only

ACS Installed

No

Detector Adj/Noun

none

Onboard DACT

No

Module Programming

Not Installed

Printer-PC

No

Module Type

Monitor

Printer Baud

9600

Module Walktest

Yes

Service Terminal Panel ID

0000

(not used)

Ring Count

0

Module Presignal

No

Primary Phone Type

Touchtone

Module Zone Assign.

000 only

Secondary Phone Type

Touchtone

Module Adj/Noun

none

DACT Communication

OFF

Zone 0 Enable

Enabled

AC Loss Delay

2

Zone 1 Enable

Enabled

Backup Reporting

First Available

Zone 2 Enable

Enabled

Primary Reporting Style

Report Point

Zone 3 Enable

Enabled

Secondary Reporting Style

Report Point

.........................through..........

.....................

Primary Account Code

0000

Zone 96 Enable

Enabled

Secondary Account Code

0000

Zones 97, 98 & 99

Enabled

Primary 24 Hour Test Time

0100

(future)

Secondary 24 Hour Test Time

0200

Loop Style

Style 4

Primary Phone Number

Loop Protocol

LITESPEED

Secondary Phone Number

Trouble Reminder

Off

Primary DACT Format

Ademco Contact ID

Banner

Secondary DACT Format

Ademco Contact ID

Time Format

12 Hr

ANN Enabled

No

Hours Setting

12

ANN-BUS Modules Addr. 1 - 8

None

Minutes Setting

00

ANN-S/PG Port

Parallel

Second Settings

ANN-S/PG Baud

9600

AM-PM Setting

AM

ANN-S/PG Data Bits

7

Month Setting

01

ANN-S/PG Parity

Even

Day Setting

01

ANN-S/PG Stop Bits

1

Year Setting

00

ANN-S/PG Offline Timer

60

Daylight Savings

Enabled

ANN-S/PG Printer Supervision

No

Month Start Daylight Savings

March

ANN-80 Piezo Enabled

Yes

Week Start Daylight Savings

Week 2

ANN-80 Lock Enabled

Yes

Month End Daylight Savings

November

ANN-80 Acknowledge Button Enabled

Yes

Week End Daylight Savings

Week 1

ANN-80 Silence Button Enabled

Yes

Verification

OFF

ANN-80 Reset Button Enabled

Yes

PAS Timer

0

ANN-80 Drill Button Enabled

Yes

Presignal Timer

0

ANN-I/O Point/Zone

Zone

Waterflow Retard Timer

0

ANN-I/O Range

00-29

NAC 1, 2, 3 & 4 Enable

Enabled

ANN-I/O Active LEDs Only

NAC 1, 2, 3 & 4 Silenceable

Yes

ANN-RLY Relay 1

Zone 1

NAC 1, 2, 3 & 4 Type

Bell

................through.......................

............

NAC 1, 2, 3 & 4 Sync Type

System Sensor

ANN-RLY Relay 10

Zone 10

NAC 1, 2, 3 & 4 Autosilence

0

ANN-LED Point/Zone

Zone

NAC 1, 2, 3 & 4 Coding

Steady

ANN-LED Alarms/ATS (Alarm, Trbl, Supv)

ATS

NAC 1, 2, 3 & 4 Zones

Zone 000 only

ANN-LED Range

0 - 9

NAC 1, 2, 3 & 4 Silence Inhibit

No