Default programming, Appendix b – Honeywell MS-9200UDLSE User Manual
Page 197

Default Programming
MS-9200UDLS PN 52750:E1 01/27/09
197
APPENDIX B
Default Programming
The following table provides a list of the programming options and their factory default
settings.
Program Option
Factory Default
Program Option
Factory Default
Detector Programming
Not Installed
Relay 1
Alarm
Detector Type
Smoke-Photo
Relay 2
Trouble (fixed)
Detector Verification
Off
Relay 3
Supervisory
Detector Walktest
Yes
Annunciator Terminal Mode
No
Detector PAS
No
Annunciator ACS Mode
No
Detector Presignal
No
UDACT
No
Detector Zone Assign.
000 only
ACS Installed
No
Detector Adj/Noun
none
Onboard DACT
No
Module Programming
Not Installed
Printer-PC
No
Module Type
Monitor
Printer Baud
9600
Module Walktest
Yes
Service Terminal Panel ID
0000
(not used)
Ring Count
0
Module Presignal
No
Primary Phone Type
Touchtone
Module Zone Assign.
000 only
Secondary Phone Type
Touchtone
Module Adj/Noun
none
DACT Communication
OFF
Zone 0 Enable
Enabled
AC Loss Delay
2
Zone 1 Enable
Enabled
Backup Reporting
First Available
Zone 2 Enable
Enabled
Primary Reporting Style
Report Point
Zone 3 Enable
Enabled
Secondary Reporting Style
Report Point
.........................through..........
.....................
Primary Account Code
0000
Zone 96 Enable
Enabled
Secondary Account Code
0000
Zones 97, 98 & 99
Enabled
Primary 24 Hour Test Time
0100
(future)
Secondary 24 Hour Test Time
0200
Loop Style
Style 4
Primary Phone Number
Loop Protocol
LITESPEED
Secondary Phone Number
Trouble Reminder
Off
Primary DACT Format
Ademco Contact ID
Banner
Secondary DACT Format
Ademco Contact ID
Time Format
12 Hr
ANN Enabled
No
Hours Setting
12
ANN-BUS Modules Addr. 1 - 8
None
Minutes Setting
00
ANN-S/PG Port
Parallel
Second Settings
ANN-S/PG Baud
9600
AM-PM Setting
AM
ANN-S/PG Data Bits
7
Month Setting
01
ANN-S/PG Parity
Even
Day Setting
01
ANN-S/PG Stop Bits
1
Year Setting
00
ANN-S/PG Offline Timer
60
Daylight Savings
Enabled
ANN-S/PG Printer Supervision
No
Month Start Daylight Savings
March
ANN-80 Piezo Enabled
Yes
Week Start Daylight Savings
Week 2
ANN-80 Lock Enabled
Yes
Month End Daylight Savings
November
ANN-80 Acknowledge Button Enabled
Yes
Week End Daylight Savings
Week 1
ANN-80 Silence Button Enabled
Yes
Verification
OFF
ANN-80 Reset Button Enabled
Yes
PAS Timer
0
ANN-80 Drill Button Enabled
Yes
Presignal Timer
0
ANN-I/O Point/Zone
Zone
Waterflow Retard Timer
0
ANN-I/O Range
00-29
NAC 1, 2, 3 & 4 Enable
Enabled
ANN-I/O Active LEDs Only
NAC 1, 2, 3 & 4 Silenceable
Yes
ANN-RLY Relay 1
Zone 1
NAC 1, 2, 3 & 4 Type
Bell
................through.......................
............
NAC 1, 2, 3 & 4 Sync Type
System Sensor
ANN-RLY Relay 10
Zone 10
NAC 1, 2, 3 & 4 Autosilence
0
ANN-LED Point/Zone
Zone
NAC 1, 2, 3 & 4 Coding
Steady
ANN-LED Alarms/ATS (Alarm, Trbl, Supv)
ATS
NAC 1, 2, 3 & 4 Zones
Zone 000 only
ANN-LED Range
0 - 9
NAC 1, 2, 3 & 4 Silence Inhibit
No