NFPA Standard-Specific Requirements
MS-9200UDLS PN 52750:E1 01/27/09
201
NFPA 72 Proprietary Protective Signaling Systems
Figure C.3 Proprietary Protective Signaling System
Form-C relay contact programmed to
activate on Supervisory condition.
Form-C Trouble contact which will
automatically activate on any Trouble
condition.
Form-C Alarm contact programmed to
activate on General Alarm.
MS-9200UDLS Main Board
MS-9200UDLS Addressable Fire Control Panel
Notes:
1. Connection between the MS-9200UDLS and
the transmitter are supervised by the
transmitter.
2. This MS-9200UDLS/Transmitter
arrangement can be employed for NFPA 72
Proprietary Protective Signaling System.