Honeywell MS-9200UDLSE User Manual
Page 142
Programming
142
MS-9200UDLS PN 52750:E1 01/27/09
3.6.9.3 Printer/PC
A Printer or a PC can be connected to the control panel. Pressing 3 while viewing
the Option Module Screen will cause the following screen to appear:
Pressing 1 while viewing the Printer-PC Screen will program the control panel for
an unsupervised (NO SU) printer. The display will change to the Printer Baud Rate
Screen as shown below.
Pressing 2 while viewing the Printer-PC Screen will program the control panel for a
supervised (SU) printer. Printer supervision, when enabled, will typically detect the
removal of the printer cable and will detect when the printer power has been turned
off. Depending upon the brand of printer, other errors such as paper empty or
printer off-line may be detected.
The following screen will appear, which allows the programmer to select the baud
rate for the printer communication:
Pressing the number key corresponding to the desired baud rate (2 for 4800 Baud
for example) will program the control panel for the selected baud rate and return the
display to the Option Module Screen which will indicate Printer/PC PR4800 for a
supervised printer installed at 4800 baud rate.
Pressing 3 while viewing the Printer-PC Screen will program the control panel for a
PC connection. The display will return to the Option Module Screen which will
indicate Printer/PC PC for personal computer installed.
Note: The LCD-80F and the Printer/PC use the same TB8 terminal block. Only
one device can be used at any one time. Setting any option in the Printer/PC screen
to Yes will disable communications with the LCD-80F. The printer must be
installed in the same room and within 50 feet of the FACP.
OPTION MODULES
1=ANNUNCIATORS/UDACT
2=ON BOARD DACT
3=PRINTER/PC NO
Option Module Screen
PRINTER-PC
1=PRINTER NO SU NO
2=PRINTER SU YES
3=PC
NO
Printer-PC Screen
PRINTER BAUD RATE
1=2400 BAUD
2=4800 BAUD
3=9600 BAUD
Printer Baud Rate Screen