Power Supply Calculations

MS-9200UDLS PN 52750:E1 01/27/09

189

Table 7.3 contains columns for calculating current draws. For each column, calculate the current
and enter the total (in amperes) in the bottom row. When finished, copy the totals from Calculation
Column 2 and Calculation Column 3 to Table 7.4 on page 190.

Table 7.3 System Current Draw Calculations

Device Type

Calculation Column 1
Primary, Non-Fire Alarm Current
(amps)

Calculation Column 2
Primary, Fire Alarm Current
(amps)

Calculation Column 3
Secondary, Non-Fire Alarm Current
(amps)

Qty

X[current draw]=

Total

Qty

X [current draw] =

Total

Qty

X[current draw]=

Total

Main Circuit Board

1

X[0.340]=

0.340

1

X[0.360]=

0.360

1

X[0.137]=

0.137

ANN-80

[ ]

X[0.037]=

[ ]

X[0.040]=

[ ]

X[0.015]=

ANN-LED

[ ]

X[0.028]=

[ ]

X[0.068]=

[ ]

X[0.028]=

ANN-RLY

[ ]

X[0.015]=

[ ]

X[0.075]=

[ ]

X[0.015]=

ANN-I/O

[ ]

X[0.035]=

[ ]

X[0.200]=

[ ]

X[0.035]=

ANN-S/PG

[ ]

X[0.045]=

[ ]

X[0.045]=

[ ]

X[0.045]=

ACM-8RF

[ ]

X[0.030]=

[ ]

X[0.158]

1

=

[ ]

X[0.030]=

ACM-16ATF

ACM-32AF

[ ]

X[0.040]=

[ ]

X[0.056]

2

=

[ ]

X[0.040]=

AEM-16ATF

AEM-32AF

[ ]

X[0.002]=

[ ]

X[0.018]

2

=

[ ]

X[0.002]=

AFM-16ATF

AFM-32AF

[ ]

X[0.040]=

[ ]

X[0.056]

2

=

[ ]

X[0.040]=

AFM-16AF

[ ]

X[0.025]=

[ ]

X[0.065]

2

=

[ ]

X[0.025]=

LDM-32F

[ ]

X[0.040]=

[ ]

X[0.056]

3

=

[ ]

X[0.040]=

LDM-E32F

[ ]

X[0.002]=

[ ]

X[0.018]=

[ ]

X[0.002]=

LCD-80F

[ ]

X[0.064]=

[ ]

X[0.064]=

[ ]

X[0.025]=

4XTMF

[ ]

X[0.005]=

[ ]

X[0.011]

4

=

[ ]

X[0.005]=

4-wire Detector Heads

[ ]

X[ ]

5

=

[ ]

X[ ]=

[ ]

X[ ]=

Power Supervision

Relays

6

[ ]

X[0.025]=

[ ]

X[0.025]=

[ ]

X[0.025]=

CP350 & CP355

[ ]

X[0.00030]=

maximum alarm draw

for all devices

0.400

[ ]

X[0.00030]=

SD350 & SD355

[ ]

X[0.00030]=

[ ]

X[0.00030]=

SD350T & SD355T

[ ]

X[0.00030]=

[ ]

X[0.00030]=

AD350 & AD355

[ ]

X[0.00030]=

[ ]

X[0.00030]=

H350 & H355

[ ]

X[0.00030]=

[ ]

X[0.00030]=

H350R & H355R

[ ]

X[0.00030]=

[ ]

X[0.00030]=

H355HT

[ ]

X[0.00030]=

[ ]

X[0.00030]=

D350P & D350PL

[ ]

X[0.00030]=

[ ]

X[0.00030]=

D350RP & D350RPL

[ ]

X[0.00030]=

[ ]

X[0.00030]=

B501BH & B501BHT

7

[ ]

X[0.001]=

[ ]

X[0.001]=

B224RB Relay Base

[ ]

X[0.00050 ]=

[ ]

X[0.00050 ]=

B224BI Isolator Base

[ ]

X[0.00045]=

[ ]

X[0.00045 ]=

MMF-300

[ ]

X[0.00040]=

[ ]

X[0.00040]=

MMF-300-10

[ ]

X[0.00350]=

[ ]

X[0.00350]=

MDF-300

[ ]

X[0.00075]=

[ ]

X[0.00075]=

MMF-301

[ ]

X[0.000375]=

[ ]

X[0.000375]=

MMF-302

[ ]

X[0.00027]=

[ ]

X[0.00027]=

MMF-302-6

[ ]

X[0.00200]=

[ ]

X[0.00200]=

BG-12LX

[ ]

X[0.00030]=

[ ]

X[0.00030]=

CMF-300

[ ]

X[0.00039]=

[ ]

X[0.00039]=

CMF-300-6

[ ]

X[0.00225]=

[ ]

X[0.00225]=

CRF-300

[ ]

X[0.00027]=

[ ]

X[0.00027]=

CRF-300-6

[ ]

X[0.00145]=

[ ]

X[0.00145]=

I300

[ ]

X[0.00040]=

[ ]

X[0.00040]=

NAC #1

8

[ ]

X[ ]=

NAC #2

[ ]

X[ ]=

NAC #3

[ ]

X[ ]=

NAC #4

[ ]

X[ ]=

Current Draw from TB3

(nonalarm

9

)

[ ]=

[ ]

[ ]=

[ ]

[ ]=

Sum each column

10

for totals

Primary Non-Alarm =

Primary Alarm =

Secondary Non-Alarm =

Table Footnote

1. All eight ACM-8RF relays activated on a single module.
2. All annunciator LEDs on
3. LDM-32F with LEDs on
4. If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add

another 0.005 amps.

5. Refer to the Device Compatibility Document for standby current.
6. Must use compatible listed Power Supervision Relay.
7. Maximum alarm current for each sounder base is 0.015 amps which must be supplied by aux. 24VDC source.
8. Current limitation of Terminal TB3 & TB4 circuits is 2.5 amps per NAC.
9. The total standby current must include both the nonresettable/resettable (TB1 Terminals 1 & 2) and resettable

(TB1 Terminals 3 & 4) power. Caution must be taken to ensure that current drawn from these outputs during
alarm does not exceed maximum ratings specified. Current limitations of TB3 & TB4 circuits is 2.5 amps per
NAC output and 0.3 amps per special application auxiliary power output

10.Total current draw listed above cannot exceed 6.0 amps.