GT 600 / 601 Engineer’s Reference Guide
103)
Press No until your required setting is displayed,
then press Yes. The display will show:-
Available Options for Forced Walk Test are.
All Sets.
All Area/Part sets will require the zones allocated in the walk test
options to be tested.
Full Only.
In Part-Set Walk Test is not required.
Off.
Forced Walk Test is disabled.
104)
Press No until your required setting is displayed,
then press Yes. The display will show:-
Note:
Bypass. Is programmed in ten minute increments. (If the system is Unset and Set within this
bypass time, the forced Walk Test is not required).
105)
Press No to enter your required time, followed by
Yes.The display will show:-
106)
At this point you may press No to move to
the next option. The display will show:-
Or press 0 (zero) repeatedly to exit.
Reporting a Mains Fail on a PSU.
In order to report a Mains Fail on a PSU the Fault output on
the PSU would be wired to a Zone on the Control Panel.
The Zone Type would be programmed as ‘Fault’.
Program the Zone Descriptor as External PSU.
At the end of the Program Zones menu we have a menu called Program Events Tags,
enter this option and select the Zone number you have programmed as Fault.
Walk = Off
Bypass = 00 Mins
Walk = Off
Bypass = >00 Mins
Program Zone
E/E mode ?
Program Zone
Event Tags ?
Program Zone
Event Tags ?