GT 600 / 601 Engineer’s Reference Guide

17)

Press No until the setting you require is displayed.
Then press Yes. The display will show:-

Press No if programming for ID 2 (601 ONLY)
The display will show:-

At this stage the ID should be wired up and all
ID Biscuits connected. The Tamper on the Module
should also be closed.

18)

Press Yes.

19)

The system will now detect all connected Biscuits.
The display will show for example:-

20)

Press Yes for Auto

21)

All detected Biscuits are now active.

Press 0 and repeat from step 4 for ID 2.

22)

Press 0 (zero) until the display shows:-

Note: If the number of devices found does not correspond to the number fitted, check
the wiring and re-map. If after checking, devices found still does not correspond, press
No.

23)

The display will show:-

24)

Enter 1 then press Yes. The display will show:-

If the zone has not been found, the display will show Off. If the zone has
been found, the display will show the zone number.

Press Yes to continue to the next device number.

Map ID Module
On SAD 1 ?

30 Devices Found
Y: Auto N:Manual

01 Jan 00: 00: 01

Enter ID #

ID # 01 on SAD 1
= Off

Map ID Module
On SAD 2 ?