Page – RISCO Group Gardtec GT600 User Manual
Page 111
Page
109
GT 600 / 601 Engineer’s Reference Guide
Typical Novagard 2G/4G Connections
Fig 6.
Fig 7.
Fig 8.
+12V
0V
S-
ST-
R TMP
F TMP
BELL+
BELL-
SAB TMP
BELLHOLD-
STROBE-
Novagard 2G/4G
(Strobe terminals omitted)
GT 600 / 601 Control Panel
AZ1
+ -
AZ2
+ -
AZ3
+ -
AZ4
+ -
AZ5
+ -
AZ6
+ -
AZ7
+ -
AZ8
+ -
TZ
+ -
N/O Devices (PA etc)
connect across Tamper & Zone
N/C Devices
multiple devices are in series
N/C Devices
N/C Devices
N/C Devices
N/C Devices
N/C Devices
N/C Devices
Control Panel Input (Zone) Connections
Standard (2 Wire) Zone Wiring
AZ1
+ -
AZ2
+ -
AZ3
+ -
AZ4
+ -
AZ5
+ -
AZ6
+ -
AZ7
+ -
AZ8
+ -
N/C Devices
N/C Devices
N/C Devices
N/C Devices
N/C Devices
N/C Devices
6k8
6k8
6k8
6k8
6k8
6k8
6k8
6k8
N C Devices
N/C Devices
6k8
6k8
4k7
4k7
4k7
4k7
4k7
4k7
4k7
4k7
TZ
+ -
End Of Line Zone Wiring
Multiple units can only be used with BS
Standard. If using EN2/3, one unit per zone.