Special Instructions for Class I, Division 1 Hazardous Locations

10/03/2006

Appendix B, Document CI-ControlWave XFC

Page 2 of 2

Table A1 -Terminal Plate Connector Customer Wiring Connectors (Continued)

Connector Wiring

Notes

J5: Pins 1 through 9

DI/O Interface

Discrete Input/Output Field Wiring: Field I/O

wiring connector is unrated, refer to ¶ 9 of this

document *

J5: Pins 9 through 12

HSC Interface

High Speed Counter Input Field Wiring: Field

I/O wiring connector is unrated, refer to ¶ 9 of

this document *

J6: Pins 1 and 2

Input Power

Power Interface: Power connector is unrated,

refer to ¶ 9 of this document

Note: * = These wires should only be installed/removed when the item (PCB) in question is

installed/removed or when checking wiring continuity. The area must be known

to be nonhazardous before servicing/replacing the unit and before installing or

removing PCBs, Connectors or individual I/O or Power wires. Refer to ¶ 6, 7 & 8

of this document. All input power and I/O wiring must be performed in

accordance with Class I, Division 2 wiring methods as defined in Article 501-4 (b)

of the National Electrical Code, NFPA 70, for installations within the United

States, or as specified in Section 18-152 of the Canadian Electrical Code for

installation in Canada.