Emerson Process Management ControlWave XFC User Manual
Page 98
ControlWave XFC
Special Instructions for Class I, Division 1 Hazardous Locations
10/03/2006
Appendix B, Document CI-ControlWave XFC
Page 2 of 2
Table A1 -Terminal Plate Connector Customer Wiring Connectors (Continued)
Connector Wiring
Notes
J5: Pins 1 through 9
DI/O Interface
Discrete Input/Output Field Wiring: Field I/O
wiring connector is unrated, refer to ¶ 9 of this
document *
J5: Pins 9 through 12
HSC Interface
High Speed Counter Input Field Wiring: Field
I/O wiring connector is unrated, refer to ¶ 9 of
this document *
J6: Pins 1 and 2
Input Power
Power Interface: Power connector is unrated,
refer to ¶ 9 of this document
Note: * = These wires should only be installed/removed when the item (PCB) in question is
installed/removed or when checking wiring continuity. The area must be known
to be nonhazardous before servicing/replacing the unit and before installing or
removing PCBs, Connectors or individual I/O or Power wires. Refer to ¶ 6, 7 & 8
of this document. All input power and I/O wiring must be performed in
accordance with Class I, Division 2 wiring methods as defined in Article 501-4 (b)
of the National Electrical Code, NFPA 70, for installations within the United
States, or as specified in Section 18-152 of the Canadian Electrical Code for
installation in Canada.