beautypg.com

Emerson Process Management ControlWave XFC User Manual

Page 90

background image

4-2 / Specifications

CI-ControlWave XFC

Table 4-3 - RS-485 Port (COM3 – Model 3808 Intf. Port) Pin Assignments

Pin #

Signal

RS-485

Description:

RS-485 Signals

J2-1 GND Signal/Power

Ground

J2-2

TR-

Transmit/Receive Neg. I/O

J2-3

TR+

Transmit/Receive Pos. I/O

J2-4

+V

Power (for 3808)

4.3 INPUT POWER SPECIFICATIONS

Note: Voltages are dc unless otherwise specified.


Operating Range:

+6.0V to +30.0V (Shutdown occurs at +5.46V nominal)


Electrical Isolation:

None


Surge Suppression:

30V Transorb to GND

Meets ANSI/IEEE C37.90-1978


Fusing:

.375A Slow Blow

4.4 I/O BOARD SPECIFICATIONS

4.4.1 External Power Monitor Specs.


Input Signal:

Input power after fuse and Diode


Input Range:

0 to 30Vdc


Resolution: 12

Bit


Accuracy: Calibrated:

±100mV @ +25°C (+77°F)

Calibrated:

±200mV over -40 to +80°C (-40 to +176°F)

4.4.2 Power Supply Sequencer Specs.

Signals Monitored:

Input Power


Sequencer Switchpoints:

+3.3V Max. ON Switchpoint = +3.15V

+3.3V Min. OFF Switchpoint = +3.00V


+1.8V Max. ON Switchpoint = +1.72V

+1.8V Min. OFF Switchpoint = +1.64V


Sequencer Output Signals: PFDLYCLK Timing on power down 2msec after POWER-

FAIL


VIN100M timing on power Up 1800msec delay for Good
Power


POWERGOOD incoming power, 3.3V & 1.8V in Spec.